CATERPILLAR OLYMPIAN MODEL G80LG
80eKW, STANDBY RATED, 120/208 VOLTS, 60 HZ, 0.8 PF
OUTDOOR LP VAPOR GENERATOR SET
Installed NEW at Dartmouth College May of 2012 and removed from Service August of 2019
Hours – verified 289
Yearly Maintenance per Service Contract: Level two service, change oil and all filters, tune up engine, Perform all Safety and electrical checks, unit hours in Auto mode
Bare Unit with Main Breaker installed – No ATS
Currently the unit does not have a fuel source.
All weekly checks performed by College electricians.
Weekly this generator was tested under load for 20 minutes and then was run 20 minutes under no load as a cooldown procedure.
In the May of 2018, the battery tender(charger) was replaced a long with the battery as a repair.
CATERPILLAR OLYMPIAN MODEL G80LG
80eKW, STANDBY RATED, 120/208 VOLTS, 60 HZ, 0.8 PF
OUTDOOR LP VAPOR GENERATOR SET
1.1 Liquid Cooled Gas Engine
_ 80ekW Standby Rating, 60Hz, 2300RPM
_ 2009 EPA Certified
_ UL2200 Certified
_ 6.8 Liter, V-10
_ STARTING/CHARGING SYSTEM
o 12V, 30 Amp charging alternator.
_ GOVERNING SYSTEM
o Electronic Governor
_ LUBE SYSTEM
o Lubricating oil
o Oil filler and dipstick
_ AIR INLET SYSTEM
o Cartridge Type Filter
_ COOLING SYSTEM
o Radiator sized for 50 degrees C (122 degrees F)
o Coolant drain line with valve
o Qty One (1) Jacket water heater with isolation valves; 120VAC, 1500W
o Low Coolant Level Sensor
_ MOUNTING SYSTEM
- Steel skid base with lifting points
- Linear vibration isolators between base and engine-generator
1.2 Generator
_ Brushless Permanent Magnet generator
_ 2/3 pitch, random wound
_ IP23 Protection
_ Class H insulation with Class H temperature rise
_ Digital voltage regulator
_ Alternator Strip Heater
_ Cable connections located inside generator housing (NEMA compatible), side or vertical
cable entry
_ Unit Mounted Circuit Breakers
o (2) 150A, UL Listed, 80% Rated
1.3 Digital Control Panel
_ H-Series control panel, Left Hand Mounted
_ Two Four Line LCD Displays Read:
o Voltage, Current
o Power Factor
o kW, kVAR
o Low Fuel Pressure, Engine Speed
o Run Hours
o Fault History,
o Coolant Temp
o Oil Pressure
o Warnings and/or Shutdowns for:
_ Low Oil Pressure Shutdown
_ High Coolant Temperature
_ Overvoltage
_ Overspeed
_ Low Coolant Level
_ Not in Auto Position
_ Emergency stop pushbutton
_ On-Off-Manual Switch
_ Configurable for NFPA 110
_ Audible alarm for fault condition
_ RS485 Port for Remote Communication
_ Engine Run Relay